RS-NAGX 5 |
|
|
Expansion module |
|
|
for emergency stop
relay according to VDE 0113 |
|
|
CE, TÜV (UL, C-UL pending) |
|
|
5 normally open
safety and 1 normally safety closed (feedback) |
|
|
LED indicators for
status and supply diagnostic |
|
|
Easy way to increase
the number of contacts |
|
|
Compact housing |
|
|
Channel
1 and channel 2 |
|
|
24 V AC / DC
(without galvanic disconnection, but with a safety |
|
|
resistor) |
|
|
|
|
|
ca. 2,4 VA |
|
|
< 30 ms |
|
|
6 A, 250 V AC, 24 V
DC, sum of currents <16 A |
|
|
6 mA - 25°C bis + 55 °C |
|
|
|
|
|
- 25°C to + 55 °C |
|
|
1500 VA |
|
|
6 A quick acting or
4 A time lag |
|
|
|
|
(*)
We offer all devices who have a CONTACT CAPACITY of min. 100 mA at 24 V DC with hard
gold-plated contacts. In this way the CONTACT CAPACITY of min. 100
mA is only 4 mA. Please
ask our sales team!
|
Input
circuit A1 is to be connected with one of the redundant safety outputs
(13-14). Errors of the expansion unit will be announced over the feedback
control loop (Y1-Y2) and the next activation will be disabled. In
case of protected wiring (short current circuit exclusion) and regularly
tests, for example during maintenance, up to safety category 4.
|
|
|
|
|
Safety
relevant substance data Depending
on wiring (only max. values are given) |
EN ISO 13849-1: PLe,
Cat.4 MTTFd: 74,2 years / high, DC: 99% / high,
CCF:
achieved |