            DEVICE

RS-NAGT / RS-NAGT.1

 

Emergency stop and safety gate monitoring relay

 

                APPLICATIONS

with time-delayed safety output

 

                APPROVALS

CE, TÜV, UL, C-UL

 

                CONTACTS

2 normally open safety, 1 normally open time-delayed safety output

 

               

Selectable opposite polarity between channels

 

                SPECIAL CHARACTERISTICS

NAGT : 0,1s - 10s ; NAGT.1 : 0,3 - 30s (ask for the ordering number)

 

 

Ask for special versions

 

                LED

Power, channel 1, channel 2 and fault

 

               

Devices has two voltages : 1 voltage fixed : 24 V DC;

 

                OPERATING VOLTAGE

Selectable : 24,  110-127 and 230 V AC

 

               

(with galvanic disconnection/transformer)

 

                POWER CONSUMPTION

ca. 3 VA

 

                START UP DELAY / FALLBACK TIME

<150 ms/< 50 ms (undelayed)

 

                CONTACT CAPACITY max.

6 A, 250 V AC, 24 V DC

 

                CONTACT CAPACITY min. at 24V DC (*)

100 mA (*)

 

                SIMULTANEITY

Simultaneous protective door contacts : ca.75 ms

 

                ENVIRONMENTAL TEMPERATURE

- 25°C to + 50°C

 

                SWITCHING CAPACITY

1500 VA (resistive load)

 

                CONTACT SECURITY

10 A quick acting or 6 A time lag

 

               

 

 

 

 

                OPERATING MODE

                (*) We offer all devices who have a CONTACT

                 CAPACITY of min. 100 mA at 24 V DC with

                 hard gold-plated contacts. In this way the

                 CONTACT CAPACITY of min. 100 mA is only 4 mA.

                Please ask our sales team!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                CONNECTION DIAGRAM

A supply voltage must be applied to terminals A1 and A2 (for AC supplies) or terminals B1 and B2 (for DC supplies). Once the supply voltage is applied, 24V DC is available at terminal T11; power LED illuminates. Terminals T12, K21 and K22 must be connected according to the application example selected to meet the application requirements. Feedback monitoring of external devices is accomplished by a connection between terminals T34 / X1 and X2. If the application does not require external monitoring, T34 / X1 and X2 must be bridged. To start the unit, terminal T11 and T34 / X1 must be bridged (automatic reset) or a momentary bridging of T11 and T34 / X1 must take place. With all of the above in place safety contacts 13-14, 23-24 and 77-78 close. Channel 1 (K2 energized) and channel 2 (K3 energized) green LEDs illuminate to show channel status. Fault LED illuminates when a short circuit takes place, at the input stage or internally.  

(*) Special edition with hard gold-plated contacts is also available. Connecting the ground wire to PE - see page 22.

 

 

 

 

 

 

 

 

                FUNCTION CIRCUIT DIAGRAM

 

                Certifications according to

                Safety relevant substance data

                Depending on wiring (only max. values are given)

EN ISO 13849-1: PLe, Cat. 4 / PLd, Cat. 3 (time delayed)

MTTFd: 57 years / high, DC: Cat. 3: 90% / medium, Cat.4: 99% / high

CCF: achieved