Download User Manual in PDF

 

            DEVICE

RS-NAGMP / RS-NAGMP.1

 

Emergency stop

 

                APPLICATIONS

and safety gate monitoring relay

 

                APPROVALS

CE, TÜV, (UL, C-UL pending)

 

                CONTACTS

3 normally open safety, 1 normally auxiliary closed

 

               

LED indicators for status and supply diagnostic

 

                SPECIAL CHARACTERISTICS

With (NAGMP.1) and without (NAGMP) choosable opposite polarity

 

between channels

                LED

Power, Channel 1 and channel 2

 

               

24 V AC / DC (without galvanic disconnection, but with a safety resistor)

 

                OPERATING VOLTAGE

24 VDC / 12VDC (without galvanic disconnection, but with an electronic fuse)

 

               

24, 110-127, 230 V AC (with galvanic disconnection/transformer)

 

                POWER CONSUMPTION

ca. 3,5 VA / 24VDC: 1,8W / 12VDC: 1,4W

 

                START UP DELAY / FALLBACK TIME

< 300 ms / < 20 ms

 

                CONTACT CAPACITY max.

8 A, 250 V AC, 250 V DC, normally closed: 24 V AC / DC

 

                CONTACT CAPACITY min. at 24V DC (*)

10 mA

 

                SIMULTANEITY

Simultaneous protective door contacts : ca. 75 ms

 

                ENVIRONMENTAL TEMPERATURE

- 25°C to + 55°C

 

                SWITCHING CAPACITY

2000 VA (resistive load), 200 W

 

                CONTACT SECURITY

6 A quick acting or 4 A time lag

 

               

 

 

 

 

                OPERATING MODE

                (*) We offer all devices who have a CONTACT

                 CAPACITY of min. 100 mA at 24 V DC with

                 hard gold-plated contacts. In this way the

                 CONTACT CAPACITY of min. 100 mA is only 4 mA.

                Please ask our sales team!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                CONNECTION DIAGRAM

A supply voltage must be applied at the terminals A1 and A2 in order to operate the device. If this is done there is a voltage of 24V DC at the terminal T11. Terminals T12, T21, T22 and T23 have to be wired as it is shown in the application examples. To start the unit terminal T33 has to bridged with terminal T34 or terminal T34 has to get a 24V DC impulse (short time bridging of the connection terminals T33-T34). If this is done the safety-contacts 13-14, 23-24 and 33-34 are closed and 41-42 are open. The LEDs channel 1 and channel 2 illuminate. Through terminals X1 and X2 the function of an external contactor can be monitored. Terminals X1 and X2 have to be bridged in order to operate the device.

 

 

 

 

 

 

 

 

 

 

 

 

                FUNCTION CIRCUIT DIAGRAM

 

                Certifications according to

                Safety relevant substance data

                Depending on wiring (only max. values are given)

EN ISO 13849-1: RS-NAGMP: PLd, Cat.3 / RS-NAGMP.1: PLe, Cat.4

MTTFd: 73,61 years / high, DC: Cat. 3: 90% / medium, Cat. 4: 99% / high

CCF: achieved