RS-NAGL / RS-NAGL.1 |
|
|
Emergency
stop relay |
|
|
for
safety light curtains / barriers |
|
|
CE, TÜV, UL,
C-UL |
|
|
2 normally open
safety, 1 normally auxiliary closed, 1 auxiliary n. c. open |
|
|
LED indicators for
status and supply diagnostic |
|
|
With (NAGL) and without (NAGL.1) opposite
polarity between channels |
|
|
|
|
|
Channel
1 and channel 2 |
|
|
RS-NAGL / L.1: 24 V
DC (without galvanic disconnection) |
|
|
RS-NAGL: 48,
110-127, 230 V AC (with galvanic disconnection/transformer) |
|
|
24 V AC / DC
(without galvanic disconnection, but with a safety resistor) |
|
|
24 V DC: 2W, 24 V AC /
DC: 4,5 VA, other: 4,6 VA |
|
|
< 150 ms
/ < 30 ms |
|
|
6 A, 250 V AC, 250 V DC |
|
|
10 mA |
|
|
|
|
|
- 25°C to + 55°C |
|
|
1500 VA (resistive load), 100 W |
|
|
6 A quick acting
(normally open) or 4 A time lag (normally closed) |
|
|
|
|
(*)
We offer all devices who have a CONTACT CAPACITY of min. 100 mA at 24 V DC with hard
gold-plated contacts. In this way the CONTACT CAPACITY of min. 100
mA is only 4 mA. Please
ask our sales team!
|
A
supply voltage must be applied at terminals A1 and A2 in order to operate the
device. If this is done there is a voltage of 24V DC at terminal T11. T12 and
T22 must be wired as shown in the application examples. Contacts 13-14, 23-24
and 63-64 open and contact 41-42 closes. In some cases, the transmitter from
the light curtains / barrier requires a test input and is connected to output
63-64. If 63-64 does not close, the transmitter and the receiver will not
work. This output ensures that a complete system is created. To start the unit
terminal T11 must be bridged with terminal T34 through a normally open
contact (reset) or the terminal T34 must receive a 24V DC impulse (short time
bridging of the connection terminals T11-T34). If the light curtains is aligned properly and the protection zone is
free, the receiver switches. At terminal T12 there is a of
voltage 24V DC and at T22 is ground. After releasing the on button or
interrupting the connection between T11 and T34 the relays K1 and K4 deenergize. Safety outputs 13-14 and 23-24 close.
Contacts 53-54 and 63-64 remain closed, contacts 41-42 open.
|
|
|
|
|
Safety
relevant substance data Depending
on wiring (only max. values are given) |
EN ISO 13849-1: PLe,
Cat.4 MTTFd: 69,05 years / high, DC: 99% / high,
CCF:
achieved |