Expansion
modules |
|
|
|
SAFE X4 / SAFE X4.1 |
|
|
Expansion module |
|
|
for emergency stop
relay according to VDE 0113 |
|
|
CE, TÜV, UL, C-UL |
|
|
4 normally open
safety and 1 normally safety closed (feedback) |
|
|
With (SAFE X4) and
without (SAFE X4.1) opposite polarity between channels |
|
|
Easy way to increase
the number of contacts |
|
|
Compact housing |
|
|
Channel
1, channel 2 and fault |
|
|
48, 110-127, 230 V
AC (with galvanic disconnection/transformer) |
|
|
24 V AC / DC
(without galvanic disconnection, but with a safety resistor) |
|
|
|
|
|
ca. 4 VA |
|
|
- / < 50 ms |
|
|
6 A, 250 V AC, 24 V
DC, sum of currents < 16 A |
|
|
6 mA |
|
|
|
|
|
- 25°C to + 55 °C |
|
|
1500 VA |
|
|
10 A quick acting |
|
|
|
|
(*)
We offer all devices who have a CONTACT CAPACITY of min. 100 mA at 24 V DC with hard
gold-plated contacts. In this way the CONTACT CAPACITY of min. 100
mA is only 4 mA. Please
ask our sales team!
|
The
expansion module is used to increase the number of outputs of a safety relay
according to VDE 0113. Several expansion modules can be connected to one
safety relay. A supply voltage must be applied at terminals A1 and A2 in
order to operate the device. If this is done there is a voltage of 24V DC at
terminal U1. Terminals K21 and K1 must
be wired as shown in the application examples. To start the module, closed
safety circuits from the safety relay must be connected with K21 and K1 and
contacts 13-14, 23-24,
33-34, 43-44, 53-53, 63-64, 73-74 and 83-84 close. The LED´s
channel 1 and 2 illuminate. The fault LED illuminates if one or more safety
circuits are open. The fault LED will be illuminated while the expansion
module relay is operational. For
version with detachable clamps (screw - or cage clamps) ... please ask our sales team!
|
|
|
|
|
Safety
relevant substance data Depending
on wiring (only max. values are given) |
EN ISO 13849-1: PLe,
Cat.4 MTTFd: 185 years / high, DC: 99% / high,
CCF:
achieved |