SAFE T ON |
|
|
Emergency stop and safety gate monitoring
relay with immediate and |
|
|
delayed outputs |
|
|
CE, TÜV, UL, C-UL |
|
|
2 n.o., 2 n.o. start up delayed, 1 n.c. |
|
|
cross circuit
protection or single-channel |
|
|
Time delay 0,05s -
600s in 64 steps, |
|
|
automatic or
manually start with start button |
|
|
Power, channel 1,
cannel 2, channel 1 and 2 delayed-on energisation |
|
|
|
|
|
24 V AC / DC ( + 25
- 20 % ) (electronic fuse ) |
|
|
|
|
|
ca. 4,8 W |
|
|
400 ms / 30 ms |
|
|
6 A, 250 V AC, 24 V DC |
|
|
6 mA |
|
|
no |
|
|
-25°C to +55°C |
|
|
1500 VA (ohm load) |
|
|
3,6A |
|
|
|
|
(*)
We offer all devices who have a CONTACT CAPACITY of min. 100 mA at 24 V DC with hard
gold-plated contacts. In this way the CONTACT CAPACITY of min. 100
mA is only 4 mA. Please
ask our sales team!
|
If
the input circuits S11, S12 and S21, S22 are closed and the start button is
released, the safety circuits 13-14, 23-24 will close. By pressing the stop
button, the safety circuits 13-14 and 23-24 open. After the set time period
has elapsed, the relay K3 and K4 energise. The safety gate switch is released
and the safety gate can be opened. By pressing the start button the relay K3
and K4 are energised, K1 and
|
|
|
|
|
Safety
relevant substance data Depending
on wiring (only max. values are given) |
EN ISO 13849-1 / EN 62061: PLe, Cat. 4 / SIL3,
SIL CL3 PFH: 3,4*10-9 1/h,
PFD: 9,32*10-6 1/h, SFF: 94% MTTFd: >100 years / high, DC: 99% / high, CCF: achieved |