Emergency stop and safety gate monitoring relays |
|||
|
|
SAFE 5 / SAFE 5.1 |
||
|
|
Emergency
stop |
||
|
|
and safety gate
monitoring relay |
||
|
|
CE, TÜV, UL, C-UL |
||
|
|
2 normally open safety |
||
|
|
LED indicators for
status and supply diagnostic |
||
|
|
|
||
|
|
With (SAFE 5) and
without (SAFE 5.1) start control |
||
|
|
Power, channel 1 and channel 2 |
||
|
|
|
||
|
|
24 V AC / DC
(electronic fuse) |
||
|
|
|
||
|
|
ca. 1,6 VA / 1,6 W |
||
|
|
< 50 ms
/ < 80 ms (AC) , < 50 ms (DC) |
||
|
|
6 A, 250 V AC, 24 V DC |
||
|
|
6 mA |
||
|
|
|
||
|
|
-25°C to + 55°C |
||
|
|
1500 VA (resistive
load) |
||
|
|
6,3 A quick acting
or 4 A time lag |
||
|
|
|
||
|
(*)
We offer all devices who have a CONTACT CAPACITY of min. 100 mA at 24 V DC with hard
gold-plated contacts. In this way the CONTACT CAPACITY of min. 100
mA is only 4 mA. Please
ask our sales team!
|
A
supply voltage must be applied via emergency stop to terminals A1 and A2.
Power LED illuminates if the emergency stop is closed. To start the unit
terminals Y2 and Y1 must be bridged with a normally open contact. The unit
works if you close this contact. At this time the contacts 13-14, 23-24 are
closed. The LEDs channel 1 and channel 2
illuminate. In series to this start button an external contactor can be
controlled. For
version with detachable clamps (screw - or cage clamps) ... please ask our sales team!
Not-Halt E-Stop |
||
|
|
|
||
|
Safety
relevant substance data Depending
on wiring (only max. values are given) |
EN ISO 13849-1: PLe,
Cat. 3 (***see product-navigator page 4) MTTFd: 71 years / high, DC: 90% / medium CCF: achieved |