SAFE 2.2 |
|
|
Mat and contact
edges control relay |
|
|
|
|
|
CE, TÜV, UL, C-UL |
|
|
2 normally open safety |
|
|
LED indicators for
status and supply diagnostic |
|
|
Safety category 4,
opposite polarity between channels |
|
|
without
start control |
|
|
Power, channel 1 and channel 2 |
|
|
|
|
|
24 V AC / DC
(electronic fuse) |
|
|
|
|
|
ca. 2,5 VA / 2,5 W |
|
|
< 50
ms /
< 30 ms |
|
|
6 A, 250 V AC, 24 V DC |
|
|
1 mA |
|
|
Simultaneous
protective door contacts : ca.40 ms |
|
|
-25°C to + 55°C |
|
|
1500 VA (resistive load) |
|
|
6,3 A quick acting
or 4 A time lag |
|
|
|
|
(*)
We offer all devices who have a CONTACT CAPACITY of min. 100 mA at 24 V DC with hard
gold-plated contacts. In this way the CONTACT CAPACITY of min. 100
mA is only 4 mA. Please
ask our sales team!
|
A
supply voltage must be applied to terminals A1 and A2. Power LED illuminates
and 24V DC is available at terminal S11. Terminals S12 and S22 must be
connected according to the application example selected to meet the
application requirements. To start the unit terminals S33 and S34 must be bridged
with a normally open contact. The unit works if you close this contact. At
this time the contacts 13-14 and 23-24 are closed. The LEDs
channel 1 and channel 2 illuminate. In series to this start button an
external contactor can be controlled. SAFE 2.2 can be used as control relay
for safety mats and safety contact edges. These mats and edges must work like
a normally opened contact. If someone steps on the mats or presses the
contact edges the normally opened contact closes and SAFE 2.2 detects this.
|
|
|
|
|
Safety
relevant substance data Depending
on wiring (only max. values are given) |
EN ISO 13849-1: PLe,
Cat.4 MTTFd: 69 years / high, DC: 99% / high,
CCF:
achieved |