Emergency stop and safety gate monitoring relays |
|
|
|
SAFE 2 / SAFE 2.1 |
|
|
Emergency
stop |
|
|
and safety gate monitoring relay |
|
|
CE, TÜV, UL, C-UL |
|
|
2 normally open safety |
|
|
LED indicators for
status and supply diagnostic |
|
|
|
|
|
With (SAFE 2) and
without (SAFE 2.1) start control |
|
|
Power, channel 1 and channel 2 |
|
|
|
|
|
24 V AC / DC
(electronic fuse) |
|
|
|
|
|
ca. 2,5 VA / 2,5 W |
|
|
< 50
ms /
< 30 ms |
|
|
6 A, 250 V AC, 24 V DC |
|
|
6 mA |
|
|
|
|
|
-25°C to + 55°C |
|
|
1500 VA (resistive load) |
|
|
6,3 A quick acting
or 4 A time lag |
|
|
|
|
(*)
We offer all devices who have a CONTACT CAPACITY of min. 100 mA at 24 V DC with hard
gold-plated contacts. In this way the CONTACT CAPACITY of min. 100
mA is only 4 mA. Please
ask our sales team!
|
A
supply voltage must be applied to terminals A1 and A2. Power LED illuminates
and 24V DC is available at terminal S11. Terminals S12 and S22 must be
connected according to the application example selected to meet the
application requirements. To start the unit terminals S33 and S34 must be bridged
with a normally open contact. The unit works if you close this contact. At
this time the contacts 13-14 and 23-24 are closed. The LEDs
channel 1 and channel 2 illuminate. In series to this start button an
external contactor can be controlled.
|
|
|
|
|
Safety
relevant substance data Depending
on wiring (only max. values are given) |
EN ISO 13849-1: PLe,
Cat.4 MTTFd: 69 years / high, DC: 99% / high,
CCF:
achieved |